Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* UNDERGROUND COVERED NO INSPECTION FILL UNUSED OPENINGS CORRECTLY LABEL PANEL AND BREAKERS NEED BUSHINGS FOR CABLE PROTECTOIN MISSING FACE PLATE ELECTRIC IN CEILING COVERED NO INSPECTION ELEC ROOM UNDERGROUND COVERED NO INSPECTION CONTROL CENTERS ENERGIZED NO INSPECTION NEED LETTER VERIFING TORQUE SETTINGS OF SECTION ASSEMBLE LABEL PANEL AND BREAKERS CLEAN SURFACE UNDER GROUND BAR SHEET METAL SCREWS NOT ALLOWED TO ATTACH GROUND BAR ELECTRIC IN CEILING COVERED NO INSPECTION OPERATOR ROOM UNDERGROUND COVERED NO INSPECTION CEILING ELECTRIC COVERED NO INSPECTION MSSING COVER PLATE |
|
| 02/07/2001 | ELECTRIC - FINAL | Denied | A/C DISCONNECT GROUND LUG HAS MILTIPULE CONDUTORS DISCONNECT NORTH SIDE USE CORRECT DISCONNECT ONE RECEPTACLE NOT 3 RECEPTACLE CORRECTLY IDENTIFY CONDUCTORS TO VOLTAGES BATHROOM ELECTRIC IN CEILING COVERED NO INSPECTION SERVICE CT CANS LOCKED NO ACCESS UFFER INSTALLED NO INSPECTION NEED GROUNDING ELECTRODE SYSTEM WELL PUMPS AND SITE LIGHTING UNDERGROUND INSTALLED NO INSPECTION LIGHT POLES INSTALLED NO INSPECTION |