Permit Details

Status:
Closed
Type:
COMMERCIAL NEW
Address NEW:
12635 W MILE WIDE RD
Apply Date:
09/02/1999
Applicant:
THURESON, WAYNE EDWARD
Description:
10 MILLION GAL RESERVOIR & BOOSTER STATION 1.54000 SF (300 x 180) RESERVOIR, REINFORCED CONCRETE RETAINING WALL AND ALUMINUM ROOF SYSTEM 2.1200 SF (60 x 20) CONTROL BUILDING CMU WALLS W/ WOOD ROOF TRUSSES,PLYWOOD SHEATHING AND METAL ROOFING 3.36000 GALLON (12DIA. x 48) HYDROPNEUMATIC TANK OF STEEL
Contractors:
  • BORDERLAND CONSTRUCTION COMPANY

Outstanding Activity Conditions

Permit Number - T99CM04223
Permit Status: Closed
Permit Description: 10 MILLION GAL RESERVOIR & BOOSTER STATION 1.54000 SF (300 x 180) RESERVOIR, REINFORCED CONCRETE RETAINING WALL AND ALUMINUM ROOF SYSTEM 2.1200 SF (60 x 20) CONTROL BUILDING CMU WALLS W/ WOOD ROOF TRUSSES,PLYWOOD SHEATHING AND METAL ROOFING 3.36000 GALLON (12DIA. x 48) HYDROPNEUMATIC TANK OF STEEL
Total Outstanding Activity Conditions - 5
Date Name
05/01/2000 SPECIAL INSPECTION FOR CONCRETE IS REQUIRED..
05/01/2000 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.
05/01/2000 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.
05/01/2000 SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED.
05/01/2000 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.

Outstanding Inspections

Permit Status: Closed
Permit Number: T99CM04223
Permite Description: 10 MILLION GAL RESERVOIR & BOOSTER STATION 1.54000 SF (300 x 180) RESERVOIR, REINFORCED CONCRETE RETAINING WALL AND ALUMINUM ROOF SYSTEM 2.1200 SF (60 x 20) CONTROL BUILDING CMU WALLS W/ WOOD ROOF TRUSSES,PLYWOOD SHEATHING AND METAL ROOFING 3.36000 GALLON (12DIA. x 48) HYDROPNEUMATIC TANK OF STEEL
Total Outstanding Inspections - 28
Last Inspection Date Description Inspector Results Comments
EXCAVATION/LAYOUT REBAR & ZON N/A Not Inspected
STEM WALL/RETAINING WALL N/A Not Inspected
BUILDING PRE-SLAB N/A Not Inspected
REINFORCED MASONRY PRE-GROUT N/A Not Inspected
EXT METAL CLIPS/EXT SHEATHING N/A Not Inspected
ROOF NAILING N/A Not Inspected
FRAMING N/A Not Inspected
SHEET ROCK NAILING N/A Not Inspected
BUILDING - FINAL N/A Not Inspected
ELECTRIC - UNDERGROUND N/A Not Inspected
ELECTRIC - ABOVE CEILING N/A Not Inspected
OUTDOOR LIGHTING FINAL N/A Not Inspected
PLUMBING - ROUGH, SOIL N/A Not Inspected
PLUMBING - INTERMEDIATE N/A Not Inspected
PLUMBING - ABOVE CEILING N/A Not Inspected
PLUMBING - GAS PRESSURE TEST N/A Not Inspected
SEPTIC - SYSTEM N/A Not Inspected
PLUMBING - PROGRESS N/A Not Inspected
PLUMBING - FINAL N/A Not Inspected
MECHANICAL - INTERMEDIATE N/A Not Inspected
MECHANICAL - PROGRESS N/A Not Inspected
MECHANICAL - FINAL N/A Not Inspected
BOILER UNFIRED PRESSURE VESSEL N/A Not Inspected
BOILER FINAL N/A Not Inspected
02/07/2001 ELECTRIC - FINAL N/A Denied A/C DISCONNECT GROUND LUG HAS MILTIPULE CONDUTORS
DISCONNECT NORTH SIDE USE CORRECT DISCONNECT ONE RECEPTACLE NOT 3 RECEPTACLE CORRECTLY IDENTIFY CONDUCTORS TO VOLTAGES
BATHROOM ELECTRIC IN CEILING COVERED NO INSPECTION
SERVICE CT CANS
LOCKED NO ACCESS
UFFER INSTALLED NO INSPECTION NEED GROUNDING ELECTRODE SYSTEM
WELL PUMPS AND SITE LIGHTING
UNDERGROUND INSTALLED NO INSPECTION
LIGHT POLES INSTALLED NO INSPECTION
02/07/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*
UNDERGROUND COVERED NO INSPECTION
FILL UNUSED OPENINGS
CORRECTLY LABEL PANEL AND BREAKERS
NEED BUSHINGS FOR CABLE PROTECTOIN
MISSING FACE PLATE
ELECTRIC IN CEILING COVERED NO INSPECTION
ELEC ROOM
UNDERGROUND COVERED NO INSPECTION
CONTROL CENTERS ENERGIZED NO INSPECTION
NEED LETTER VERIFING TORQUE SETTINGS OF SECTION ASSEMBLE
LABEL PANEL AND BREAKERS
CLEAN SURFACE UNDER GROUND BAR
SHEET METAL SCREWS NOT ALLOWED TO ATTACH GROUND BAR
ELECTRIC IN CEILING COVERED NO INSPECTION
OPERATOR ROOM
UNDERGROUND COVERED NO INSPECTION
CEILING ELECTRIC COVERED NO INSPECTION
MSSING COVER PLATE
05/25/2000 ELECTRIC - UFER N/A Correction Required ADDTL COMMS - NO PLANS NO PERSON WITH KNOWLEDGE OF INSPECTION REQUEST NO UFER PLEASE RECALL
06/28/2000 ELECTRIC - INTERMEDIATE N/A Correction Required ADDTL COMMS - ALREADY COVERED PLEASE UNCOVER AND RECALL