Permit: T21CM09453

Parcel: 11620637A


Addresses:

165 S LINDA AV

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Above Ceiling 

Date Description Inspector Results Comments
01/09/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass Level #], Section A room units: S330, S329, S356, S358, S360, S340, S339, S338, S337, S336, S335, S333, S334, S331.
01/14/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass Level #3. Area B: Room units S355, S354, S353, S351, S350, S348, S349, S347, S346, S345, S344, S343, S342, S341, S359, S357.
02/23/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass Commercial suites at North Building; Ok to set ceiling tiles.
03/09/2026 COT - HCEL - Electrical Above Ceiling  Not Ready
04/09/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 4-9-26: MEP's at 1st. floor corridor (south side Courtyard A)-fire caulk penetrations at west end of corridor and above elevator, add supports to DWV at intervals of 4', add clamps to secure AWG wires every 4', fire caulk horizontal penetrations at corridor rated walls. Room's 508, 507-flex is severely crush and repairs shall be made to avoid loss of airflow, 506-add a support to exhaust in bedroom to avoid sagging, 505-seal opening above ceiling with drywall at bedroom, add supports to hvac whip and remove from ceiling grid. Per NEC 300.1.1(B), awg wires cannot be zip tied to ceiling grids-make corrections by adding supports using an independent approved method (applies to room's 508, 507, 506, and 505).
04/14/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 4/14/26: ABOVE CEILING IN CORRIDOR A approved in north building ok to proceed.
04/22/2025 COT - HCEL - Electrical Above Ceiling  Canceled
04/28/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass Above at drop ceilings approved in rooms 527,525,524,501,502,503,506,508. Okay to proceed progress areas.
Re walk 504,505,507 4/28/2026
04/29/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 4/29/2026 Re walk 504,507,515,520
505,528,512,513,514,517,518,519
401&402 in wall MEP approved.
05/01/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 5/1/2026 All corrections were made in rooms 504,507,515. Above ceiling at drop lids.
Pending 520. Okay to proceed progress areas.
05/07/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 5/7/2026 partial pass. Commercial unit 119 above ceiling and 520.
121 not ready.
05/14/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass
COT - HCEL - Electrical Above Ceiling  Canceled
06/01/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 6/1/2026 partial pass. 5th floor all corridors approved.
06/02/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 6/1/2026 partial pass. 5th floor all corridors areas need fire caulking or rock wool.

6/2/2026 partial pass. 5th floor all corridors corrections were completed. Okay to proceed progress areas.
06/17/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass 6-17-25: electrical above ceiling for room's 531, 532, 534, 533, 535, 536, 538 verified per plans. Okay to continue with construction at progress areas.
06/23/2025 COT - HCEL - Electrical Above Ceiling  Partial Pass
07/16/2026 COT - HCEL - Electrical Above Ceiling  Not Ready
07/28/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 7-28-26: Inspection of MEP's above ceiling at garage entryway- add ground screws to 6-metal boxes. Penetrations above ceiling grid properly fire caulked and DWV supported. Will need to verify ground screws but okay to continue with construction at progress areas.
08/27/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 8/27/2026 partial pass. Drop ceilings 5th floor unit 526. 4th floor unit 408 approved. Okay to proceed progress areas.
09/03/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 9-3-26: above ceiling MEP's at 408, 407, 405, 406-ground screw required at metal junction box at living room, 404-add straps to restroom exhaust, make corrections to dev above ceiling at living room and fire caulk penetrations, 403, 402-ground metal pancake boxes above ceiling, 401-ground metal pancake boxes, 424-ground pancake boxes, 425-ground pancake boxes, 426-ground screw at metal junction boxes, 428-same, 427-same
09/04/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 9-4-26: 412-move smoke detector over away from ceiling grid, 413, 414-secure line set from grid, 415-secure exhaust in bedroom, 416-secure line set from grid in living room, 418-remove line set from ceiling grid. Have electricians walk units from 9/3/26 and ground all metal boxes above ceiling. Stopped inspection-additional items may be noted.
09/08/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass 9/9/26: MEP's above ceiling at room's 407, 406, 405, 404, 403, 402-pending ground at living room metal box, 401-same, 424, 425, 426, 428, 427, 412-move smoke detector out of ceiling grid area, 413, 414, 415, 416, 418, 417, 419, 420-adjust supports at bedroom exhaust, 424, 161. Unit's not noted with required corrections are okay to cover
09/16/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass
09/18/2026 COT - HCEL - Electrical Above Ceiling  Partial Pass
10/16/2024 COT - HCEL - Electrical Above Ceiling  Not Ready Contractor cancelled.
10/29/2024 COT - HCEL - Electrical Above Ceiling  Partial Pass Level#1. Room units S141, S143, S144, S148, S159
12/10/2024 COT - HCEL - Electrical Above Ceiling  Partial Pass Level #2, Room units: S229, S230, S231, S232, S233, S234, S235, S236, S238, S239, S240, S241, S256, S258, S260