Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Intermediate
Permit Number - T21CM09453
Inspection Description - COT - HCEL - Electrical Intermediate
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | Level #2, Section A room units:S330, S329, S356, S358, S360, S340, S339, S338, S337, S336, S335, S333, S334, S331. | |
| 01/14/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | Level #3, Area B: Room units S355, S354, S353, S351, S350, S348, S349, S347, S346, S345, S344, S343, S342, S341, S359, S357. | |
| 03/04/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | In wall electric for units: 242, 246, 247, 248, 257, 259. | |
| 05/01/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | 3/19/25: section A rooms, 431,432,434,433,435,436,439,440 ( Not ready will need to re-inspect rooms) 3/25/25: Section A 4th floor rooms (441,460,459,458,457,456) not ready multiple issues need to be addressed prior to re-inspection. 3rd floor room 352 not ready 3/28/25: Section B 4th floor rooms (455,454,453,452,451,450,449,448,446) Not ready multiple issues need to be addressed prior to re-inspection. 4/3/25: Re-inspection required with fee 5/1/25: Electrical intermediate in rooms 557,558,559,560,536 approved. |
|
| 06/20/2025 | COT - HCEL - Electrical Intermediate | Partial Pass | 6-20-25: rough electrical on room's 172, 173, 174, 175 (secure awg wires to framing within 12" of wires exiting a box and staple every 4' thereafter & firefoam penetrations at top plates), 170-add staple within 12" of awg wires exiting a box, 169-firefoam penetrations at blocking or top plates,168-staple awg within 12" of light switch and every 4' thereafter, firefoam DWV at penetrations. Items mentioned will be verified at intermediates-okay to continue with construction. | |
| 10/15/2024 | COT - HCEL - Electrical Intermediate | Partial Pass | Electric room #116; Ok to Sheetrock throughout. | |
| 10/23/2024 | COT - HCEL - Electrical Intermediate | Not Ready | Will reschedule for 24 October. | |
| 10/24/2024 | COT - HCEL - Electrical Intermediate | Partial Pass | In wall electric in room units; S133, S135, S138, S139, S140, S157, S158, S160. | |
| 10/29/2024 | COT - HCEL - Electrical Intermediate | Partial Pass | Level #1 in wall electric in room units S141, 143, 144, 148, 159. OK to insulate and cover walls. | |
| 12/10/2024 | COT - HCEL - Electrical Intermediate | Partial Pass | Level #2 Room units: S229, S230, S231, S232, S233, S234, S235, S236, S238, S239, S240, S241, S256,S258, S260 |