Permit: T17CM00004

Parcel: 12404097C


Addresses:

950 N TYNDALL AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T17CM00004

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2019 FIRE - FINAL Approved OK FOR COFO FIRE ALARM PERMIT TO REMAIN OPEN
08/29/2019 FIRE - FINAL Partial Approval Items needed for a COFO from Fire
2-way communication needs to be installed, operable and communicating with a central station
check all fire alarm breakers and lock out. Batteries need to be dated
North address needs to be installed
exterior stairwell signs need to be added to the 4 stairwells
need : sprinkler panel, stariwell pressurization, FACP, elevator, generator two-way communication signs in r/w or b/w 3" letters for the fcc room
close and cover all FA junction covers and modules
need to check all door and patio hardware for proper operation
need to connect and test the access control and the fire alarm
delayed egress needs to be connected to the fire alarm
need to perform the audibility intelligibility test of the fire alarm '
fire alarm required to be 75 db at the pilow hieght
need paperwork from Jensen Hughes for the smoke control system
all elevators need to be comissioned and the paperwork provided
08/28/2019 FIRE - FINAL Partial Approval Approved the fire alarm and fire sprinkler for the 10th floor and the roof. Ok to issue a TCO for 10 and the roof.
08/23/2019 FIRE - FINAL Partial Approval 9th floor tested the fire alarm and performed the fire sprinkler final. Ok for TCO for 9th floor to occupy.
08/21/2019 FIRE - FINAL Partial Approval Temp COFO issued by building for 1-7. Yesterday we completed the walk of 8 missing the 7 stack so now they are complete on 8 and fire is ok with a TCO being issued for 8. Floors 9, 10 and the pool are still under construction. They have a building separation plan in place for the construction of 9, 10 and roof that was approved on paper and on-site by fire and building.
08/15/2019 FIRE - FINAL Partial Approval 1) fire alarm is not complete and is not GREEN
2) Emergency Responder Radio Coverage was tested but signals were not confirmed to the fire alarm system
3) Two-way communication is installed but is not operable
4) doors do not self latch
5) doors that are on alarms are not programmed nor do they hold open
6) Elevators are not commissioned
7) East side holds the ourside area of assisted rescue. We do not have a clear egress on this side
8) Front entry does not have proper egress
9) Parking garage does not have access
10) fire pump room is blocked and the egress is not landscaped ie Concrete path
11) seperation per plan for occpancy is NOT installed.
NOT READY FOR INSPCETION TOO MANY ITEMS ARE NOT READY. WILL GET WITH THEM REGARDING WEEKEND PLAN AND FIRE WATCH. MUST COMPLETE ERESS ISSUES AND PENDING BCO APPROVAL.
05/14/2019 FIRE - FINAL Partial Approval Tested the fire pump today. Confirmed water flow, tamper and fire pump signals to the offsite fire monitorint. APPROVED FOR TCO TO FIXTURE