Case: T16DV03044

Parcel: 13727643A


Addresses:

1970 W VALENCIA RD

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
05/20/2016 INSP - INITIAL CODE ENFORCMENT Approved Inspector GG and I met with maintenance. We looked at both pools There are two pools on this property. Both pool had electrical concerns. There are broken connections and fittings at the motors. There are missing the bonding wires for the motors and the heaters. There are junction boxes open and missing covers. There is junction boxes with bent and open covers allowing moisture and environment in. There is switch covers that are missing flip covers also allowing environment in. There are problems inside the Electric panels. One of the panels the front pool has melted wires and double tapping on the breakers. The other panel has neutral conductors being used as hot conductors. Labeling is missing on both panels. Talked to the maintenance personnel about the hazards associated and how an electrical contractor will be needed due to the nature of the hazards. I let him know that permits will be required for work. I will return with paperwork on Monday or Tuesday for the NOV. Met with the manager and issued a "Do Not Enter" order and shut both pools down. Left a NOV for emergency abatement with her, she sign the copy. Instructed her to go ahead and lock out both pools at this point.