Permit: T06CM02271

Parcel: 13819029B


Addresses:

155 W VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/19/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
1) SUBJECT TO POSTING OF BOND
2) SERVICE OK-GROUNDING OK
12/18/2007 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1. BOND JUMPER IS ALREADY INSTALLED IN SERVICE DISCONNECT, REMOVE 1/0 GROUND FROM NEUTRAL BAR & TERMINATE TO ENCLOSURE
2. PHASE GROUND WIRING AT SERVICE
GROUND WIRE FOR BLD. STEEL & WATER MUST BE SUPPORTED TO BLD. STRUCTURE NOT CONDUITS
3. REMOVE POLE COVERS