Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) SUBJECT TO POSTING OF BOND 2) SERVICE OK-GROUNDING OK |
|
| 12/18/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. BOND JUMPER IS ALREADY INSTALLED IN SERVICE DISCONNECT, REMOVE 1/0 GROUND FROM NEUTRAL BAR & TERMINATE TO ENCLOSURE 2. PHASE GROUND WIRING AT SERVICE GROUND WIRE FOR BLD. STEEL & WATER MUST BE SUPPORTED TO BLD. STRUCTURE NOT CONDUITS 3. REMOVE POLE COVERS |