Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/22/2009

Applicant:

GOLDEN PINS LLC

Description:

Full Fire Prevention Inspection. Gary Campbell 888-4272

Outstanding Inspections

Case Number: T09FR02017
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
06/22/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____1. Address numbers shall be in accordance with Pima County address display requirements. NOTE: See attached form.
06/22/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1. The fused power tap located in the Pro Shop back room shall be removed due to a damaged cord.
06/22/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. _____1. The fused power taps located behind the counter in the Pro Shop shall be plugged directly into an outlet and not into another power tap .
06/22/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing cover for the electrical outlet located in the front office. _____2. Replace the missing cover for the electrical outlet located in the Pro Shop by the bowling balls. _____3. Replace the two electrical outlet covers located in the Pro Shop back room. _____4. All open spaces in the electrical panels located in the back machine area shall be coved with an approved electrical blank.
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service, test and tag the automatic sprinkler system and provide the inspection report. _____2. Remove the wire from the Fire Department Connection and repair the coupling so they swivel easily.
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. The hood systems shall be cleaned professionally to remove the accumulation of grease. NOTE: provide documentation of the cleaning. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
06/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. The double-keyed lock located on the office door shall be replaced with a thumb-turn lock. _____2. The double-keyed lock located on the Pro Shop door shall be replaced with a thumb-turn lock. _____3. The double-keyed locks located on the west EXIT doors shall be disabled to prevent their use. _____4. Remove the locking hasp from the west end storage door. _____5. The double-keyed locks located on the east EXIT doors shall be disabled to prevent their use. _____6. The double-keyed lock located on the east end meeting room door shall be replaced with a thumb-turn lock.
06/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above both main entrance doors.
06/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____1. Remove the old drop-bar hardware from the east door located in the back machine area.
06/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The EXIT sign located in the east end meeting room shall be illuminated. _____1. Replace the burned out bulb in the EXIT sign located above the lounge west exit door.
06/22/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: _____1. Repair the emergency lighting unit located by the pool tables. _____2. Repair the emergency lighting unit located by the front desk.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02017
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/11/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been abated.