Case: T09FR02017

Parcel: 10706005B


Addresses:

1010 W MIRACLE MILE


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR02017

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/22/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:
2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background.

_____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above both main entrance doors.
06/22/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1. The double-keyed lock located on the office door shall be replaced with a thumb-turn lock.

_____2. The double-keyed lock located on the Pro Shop door shall be replaced with a thumb-turn lock.

_____3. The double-keyed locks located on the west EXIT doors shall be disabled to prevent their use.

_____4. Remove the locking hasp from the west end storage door.

_____5. The double-keyed locks located on the east EXIT doors shall be disabled to prevent their use.

_____6. The double-keyed lock located on the east end meeting room door shall be replaced with a thumb-turn lock.
06/22/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8.5 Unlatching. The unlatching of any door or
leaf shall not require more than one operation.

_____1. Remove the old drop-bar hardware from the east door located in the back machine area.
06/22/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1. The EXIT sign located in the east end meeting room shall be illuminated.

_____1. Replace the burned out bulb in the EXIT sign located above the lounge west exit door.
06/22/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:

_____1. Repair the emergency lighting unit located by the pool tables.

_____2. Repair the emergency lighting unit located by the front desk.