Case: T09FR02017

Parcel: 10706005B


Addresses:

1010 W MIRACLE MILE


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR02017

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/22/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.

_____1. Replace the missing cover for the electrical outlet located in the front office.

_____2. Replace the missing cover for the electrical outlet located in the Pro Shop by the bowling balls.

_____3. Replace the two electrical outlet covers located in the Pro Shop back room.

_____4. All open spaces in the electrical panels located in the back machine area shall be coved with an approved electrical blank.
06/22/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.4.2 Power supply. Relocatable power taps shall be
directly connected to a permanently installed receptacle.

_____1. The fused power taps located behind the counter in the Pro Shop shall be plugged directly into an outlet and not into another power tap
.
06/22/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.

_____1. The fused power tap located in the Pro Shop back room shall be removed due to a damaged cord.