Case: T09FR02017

Parcel: 10706005B


Addresses:

1010 W MIRACLE MILE


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR02017

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.

_____1. Service, test and tag the automatic sprinkler system and provide the inspection report.

_____2. Remove the wire from the Fire Department Connection and repair the coupling so they swivel easily.
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

_____1. The hood systems shall be cleaned professionally to remove the accumulation of grease.
NOTE: provide documentation of the cleaning.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.

All noted Tucson Fire Code violations have been corrected: _____/_____/_____