Case: T08FR04366
Case Details
Entered Date:
11/18/2008
Applicant:
BROADWAY-CRAYCROFT LLC
Description:
The Specialists - 751-8500 Initial inspection 11/17/08, RI 3/31/09, Report Delivered 4/13/09 Business Representative: ______________ I have received a copy of this report and understand the corrections needed: ________________ Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved ________, Re-inspections: 4/13/09.
Outstanding Inspections
Case Number: T08FR04366
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 16
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2009 | VIOL - EMERGENCY PLAN/PREPARE | DGREENLE | Violation | TFC 407.2 - Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. _____ Provide MSDS for all hazardous materials. |
04/06/2009 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Violation | TFC 504.2 - Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. _____ Unblock rear door. _____ Open East door as required in most recently permitted plans or obtain as-built permits to eliminate it. |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. Remove unapproved cube adaptors _____ above window E. of front door |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. _____ Remove unapproved relocatable power tap in office. |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. TFC 605.5 - Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. _____ Replace unapproved extension cord with approved relocatable power tap - sales counter. |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.4.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. _____ Provide approved impact protection for power cord at sales desk. _____ Remove cord extending through ceiling tiles above window East of front door. |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.5.3 - Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage. _____ Remove damaged extension cords (temp bay). |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.6 - Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____ Switchplates in Home Theater showroom _____ Junction Box in Office _____ Flourscent Light in Office _____ Outlet below counter behind sales desk. |
04/06/2009 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Violation | TFC 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____ Repair 1 hour fire-rated wall. _____ Replace missing ceiling tiles or remove remaining without comprimising 1 hr fire rating. _____ Get confirmation (by licenced contractor) of 1 hr fire rating for entire wall and interior doors. |
04/06/2009 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Violation | TFC 703.2 - Opening protectives Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. _____ Remove hold-open device from fire door. |
04/06/2009 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Violation | TFC 703.2.1 - Signs Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch high to read as follows: For doors designed to be kept normally closed: FIRE DOOR-KEEP CLOSED. _____ Provide approved sign for fire door. |
04/06/2009 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | Chapter 906, Portable Fire Extinguishers TFC 906.1 - Where required. Portable fire extinguishers shall be installed in the following locations: 3. In areas where flammable or combustible liquids are stored, used or dispensed. * 5. Where required by the sections indicated in Table 906.1.** TFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Professional maintenance yearly, manual inspection monthly, affix a tag to the extinguisher with records of these activities.) _____ Have all extinguishers professionally maintained and manually inspected every 30 days thereafter with records of these activities indicated on an affixed tag. TFC 906.3 - Size and distribution. For occupancies that involve primarily Class A fire hazards, the minimum sizes and distribution shall comply with Table 906.3(1).* Fire extinguishers for occupancies involving flammable or combustible liquids with depths of less than or equal to 0.25-inch shall be selected and placed in accordance with Table 906.3(2)***. *** Extra High Hazard = 40B, >30'. (due to the limited area of use, you are allowed to install a 20B within 30' of adhesive mixing, dispensing and spraying operations) _____ Provide a 20B extinguisher within 30' of adhesive mixing, dispensing and spraying operations, mounted in an approved manner. (below) TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. TFC 906.9 - Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that its top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches. ** From Table 906.1 - Additional Required Portable Fire Extinguishers Woodworking facilities - 1904.2 - Portable fire extinguishers and hose. - Portable fire extinguishers... shall be provided within 50 feet of travel distance to any machine producing shavings or sawdust. _____ Provide a 2A extinguisher for woodshop mounted in an approved manner (above). |
04/06/2009 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. |
04/06/2009 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | TFC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Exceptions: In buildings in occupancy... Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. 1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation. _____ Remove unapproved locking devices from rear door. |
04/07/2009 | VIOL - HAZARDOUS MATERIALS,GEN | DGREENLE | Violation | 2703.7.1 Smoking. Smoking shall be prohibited and "No Smoking" signs provided... In rooms or areas where flammable or combustible hazardous materials are stored, dispensed or used. Signs required by this section shall be in English as a primary language or in symbols allowed by this code and shall comply with Section 310. _____ Post approved "NO SMOKING" signs in all areas where hazardous materials are stored, dispensed and used. |
04/07/2009 | VIOL - FLAMMABLE LIQUIDS | DGREENLE | Violation | TFC 3403.5 - Labeling and signage. The fire code official is authorized to require warning signs for the purpose of identifying the hazards of storing or using flammable liquids. Signage for identification and warning such as for the inherent hazard of flammable liquids or smoking shall be provided in accordance with this chapter and Sections 2703.5 and 2703.6. TFC 3403.5.1 - Style. Warning signs shall be of a durable material. Signs warning of the hazard of flammable liquids shall have white lettering on a red background and shall read: DANGER- FLAMMABLE LIQUIDS. Letters shall not be less than 3 inches in height and 1/2 inch in stroke. _____ Provide approved signage for all areas where flammable liquids are stored, dispensed and used. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04366
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE, Occupancy Type: M/S1 (old C of O: B1/B2) Type II/Unsprinklered |
06/30/2009 | VIOL - ADMINISTRATION | DGREENLE | Approved | TFC 111.1 - Order. Whenever the fire code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the fire code official is authorized to issue a stop work order. STOP WORK ORDER: Due to the extremely flammable properties of DAP Weldwood adhesive, you are prohibited from applying it inside the building without an approved spray booth or hood. |