Case: T08FR04366

Parcel: 12803081A


Addresses:

5602 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - FIRE RESIST.RATED CONST

Case Number - T08FR04366

Inspection Description - VIOL - FIRE RESIST.RATED CONST

Inspection Status - Violation

Date Description Inspector Results Comments
04/06/2009 VIOL - FIRE RESIST.RATED CONST Violation TFC 703.1 - Maintenance
The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.

_____ Repair 1 hour fire-rated wall.

_____ Replace missing ceiling tiles or remove remaining without comprimising 1 hr fire rating.

_____ Get confirmation (by licenced contractor) of 1 hr fire rating for entire wall and interior doors.
04/06/2009 VIOL - FIRE RESIST.RATED CONST Violation TFC 703.2 - Opening protectives
Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable.

_____ Remove hold-open device from fire door.
04/06/2009 VIOL - FIRE RESIST.RATED CONST Violation TFC 703.2.1 - Signs
Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch high to read as follows:
For doors designed to be kept normally closed: FIRE DOOR-KEEP CLOSED.

_____ Provide approved sign for fire door.