Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

09/10/2008

Applicant:

RIO NUEVO MULTIPURPOSE FACILITIES DISTRICT

Description:

Full Fire Prevention Inspection. Patty Yates 547-8602

Outstanding Inspections

Case Number: T08FR02737
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
09/10/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 604.4 Operational inspection and testing. Emergency power systems, including all appurtenant components shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111. _____1.Service and test the emergency power generator and provide the documentation of the inspection report.
09/10/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Service and test the fire alarm system and provide doucmentation of the inspection report. _____2.Remove the tape from the automatic sprinkler head located in the organ South storage room.
09/10/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. _____1.Mount the portable fire extinguisher located in the Milano storage room.
09/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm)or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. _____1.Add an approved exit sign to the East exterior exit access corridor to clearly identify the exit access.
09/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Repair or replace the emergency lighting unit located in the tech booth. _____2.Repair or replace the emergency lighting unit located stage left. _____3.Repair or replace the emergency lighting unit located stage right.
09/10/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1.Remove all storage from obstructing the exit doors located in the Congress ramp exit corridor. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/10/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following method: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1.Secure the compressed gas cylinders located in the Founders lounge.

Completed Inspections

Case Status: FIELD
Case Number: T08FR02737
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/06/2009 INSP - FULL JBURGE Approved This report was referred to Glenn D' Auria.