Case: T08FR02737

Parcel: 11712037A


Addresses:

17 W CONGRESS ST


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02737

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/10/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

_____1.Service and test the fire alarm system and provide doucmentation of the inspection report.

_____2.Remove the tape from the automatic sprinkler head located in the organ South storage room.
09/10/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.

_____1.Mount the portable fire extinguisher located in the Milano storage room.