Case: T08FR02737

Parcel: 11712037A


Addresses:

17 W CONGRESS ST


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02737

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1.Repair or replace the emergency lighting unit located in the tech booth.

_____2.Repair or replace the emergency lighting unit located stage left.

_____3.Repair or replace the emergency lighting unit located stage right.
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1011.1 Where required. Exits and exit access doors shall be
marked by an approved exit sign readily visible from any direction
of egress travel. Access to exits shall be marked by readily
visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. Exit sign
placement shall be such that no point in a corridor is more than
100 feet (30 480 mm)or the listed viewing distance for the sign,
whichever is less, from the nearest visible exit sign.

_____1.Add an approved exit sign to the East exterior exit access corridor to clearly identify the exit access.
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.

_____1.Remove all storage from obstructing the exit doors located in the Congress ramp exit corridor.



________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)






______________________________
(Captain)

Full inspection done by Inspector John E. Bieg
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________