Full Fire Prevention Inspection. Patrick Healy 623-7449

Outstanding Inspections

Case Number: T08FR02624
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
09/04/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____1.Post 15 inch address numbers on the building. NOTE:See the attached Pima County Address requirements.
09/04/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 604.3.2 Written record. Written records of the inspection, testing and maintenance of emergency and standby power systems shall include the date of service, name of the servicing technician, a summary of conditions noted and a detailed description of any conditions requiring correction and what corrective action was taken. Such records shall be kept on the premises served by the emergency or standby power system and be available for inspection by the fire code official. _____1.Service and test the emergency generator and provide documentation of such work.
09/04/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove all extension cords used for permanent wiring around the customer service area. NOTE:Replace the extension cords with pused multi-plug adapters.
09/04/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. _____1.Add an automatic sprinkler head to the deli freezer for proper sprinkler coverage.
09/04/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised. _____1.Chain and padlock both control valves for the automatic sprinkler system in the open position.
09/04/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. _____1. A Class K rated portable extinguisher shall be located within 30 feet of the fryers.
09/04/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1.Clean and remove all grease accumulation from the bakery and deli hoods and provide documentation of such work.
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the loss prevention chain and locking hardware from the exit doors. _____2.Remove the padlock and locking hardware from the north egress door located in the garden center. _____3.Remove the padlock, locking bar and deouble-keyed lock from the Northeast egress door located in receiving. NOTE:Replace the double-keyed lock with a thumb-turn lock.
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors the following exists. 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1.Post the above wording above the inside of the entrance/exit doors.
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove the suface bolt from the beer cooler door.
09/04/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following method: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1.The compressed gas cylinder located in the floral frige shall be secured to prevent falling. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02624
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/29/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violation have been corrected.