Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR02624
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove all extension cords used for permanent wiring around the customer service area. NOTE:Replace the extension cords with pused multi-plug adapters. |
|
| 09/04/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 604.3.2 Written record. Written records of the inspection, testing and maintenance of emergency and standby power systems shall include the date of service, name of the servicing technician, a summary of conditions noted and a detailed description of any conditions requiring correction and what corrective action was taken. Such records shall be kept on the premises served by the emergency or standby power system and be available for inspection by the fire code official. _____1.Service and test the emergency generator and provide documentation of such work. |