Case: T08FR02624

Parcel: 115211530

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR02624

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/04/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.

_____1.Remove all extension cords used for permanent wiring around the customer service area.
NOTE:Replace the extension cords with pused multi-plug adapters.
09/04/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 604.3.2 Written record. Written records of the inspection,
testing and maintenance of emergency and standby power
systems shall include the date of service, name of the servicing
technician, a summary of conditions noted and a
detailed description of any conditions requiring correction
and what corrective action was taken. Such records shall be
kept on the premises served by the emergency or standby
power system and be available for inspection by the fire
code official.

_____1.Service and test the emergency generator and provide documentation of such work.