Case: T07FR02505
Case Details
Entered Date:
12/07/2007
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T07FR02505
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 All open spaces in electrical panels shall be covered with blanks. {Electrical room and back-up power for the registers room}. |
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4 #1.The cube adapter located in the accounting office shall be removed. #2.The cube adapter located in personel training office shall be removed. |
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 #1.Remove the extension cord used in hte invoice office. #2.Remove the extension cord used in the maintenance room. |
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 The electrical outlet located outside the northease exit door in the stock area shall have an approved cover. |
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Remove all dust and lint from the sprinkler head located by the maintenance room corner. #2.Service and test the fire alarm system and provide documentation of such work. |
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.3.3 Submit approved plans for the addition of sprinkler heads in the dairy cooler. |
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 All portable fire extinguishers shall be mounted. |
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.9 #1.The portable fire extinguisher located in electronics shall not be mounted above five feet. #2.The portable fire extinguisher located in the claims office shall not be mounted above five feet. |
12/07/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.1 Post an exit sign above the exit door by the personel office |
12/07/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4 All exit signs shall be checked for emergency illumination back-up power. |
12/07/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Repair the emergency lighting unit located by the associates lounge. |
12/07/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.5 Remove the hanging decorations obstructing the visibility of the exit sign located by the casheer station and garden center. |
12/07/2007 | VIOL - LIQUID PETROLEUM GASES | JBURGE | Correction Required | TFC 3809.14 The popane bottles located outside by the loading dock shall not be within 20 feet of any exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR02505
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |