Case: T07FR02505

Parcel: 105102420


Addresses:

455 E WETMORE RD

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
12/07/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1028.5 Remove the hanging decorations obstructing the visibility of the exit sign located by the casheer station and garden center.
12/07/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1027.4 All exit signs shall be checked for emergency illumination back-up power.
12/07/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Repair the emergency lighting unit located by the associates lounge.
12/07/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1011.1 Post an exit sign above the exit door by the personel office