Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR02505
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 #1.Remove the extension cord used in hte invoice office. #2.Remove the extension cord used in the maintenance room. |
|
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 All open spaces in electrical panels shall be covered with blanks. {Electrical room and back-up power for the registers room}. | |
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.4 #1.The cube adapter located in the accounting office shall be removed. #2.The cube adapter located in personel training office shall be removed. |
|
12/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.6 The electrical outlet located outside the northease exit door in the stock area shall have an approved cover. |