Case: T07FR02505

Parcel: 105102420


Addresses:

455 E WETMORE RD

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
12/07/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.7 All portable fire extinguishers shall be mounted.
12/07/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.9 #1.The portable fire extinguisher located in electronics shall not be mounted above five feet.
#2.The portable fire extinguisher located in the claims office shall not be mounted above five feet.
12/07/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 #1.Remove all dust and lint from the sprinkler head located by the maintenance room corner.
#2.Service and test the fire alarm system and provide documentation of such work.
12/07/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 903.3.3 Submit approved plans for the addition of sprinkler heads in the dairy cooler.