Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR02505
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 906.7 All portable fire extinguishers shall be mounted. | |
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 906.9 #1.The portable fire extinguisher located in electronics shall not be mounted above five feet. #2.The portable fire extinguisher located in the claims office shall not be mounted above five feet. |
|
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.6 #1.Remove all dust and lint from the sprinkler head located by the maintenance room corner. #2.Service and test the fire alarm system and provide documentation of such work. |
|
12/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 903.3.3 Submit approved plans for the addition of sprinkler heads in the dairy cooler. |