Case: T07FR00469
Case Details
Entered Date:
03/12/2007
Applicant:
PI KAPPA PHI PROPERTIES INC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00469
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 17
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2007 | INSP - FULL | NSPRENGE | Correction Required | |
| 03/15/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. 1)Remove accumulation of waste behind water fountain in corridor. 2) Remove accumulation of waste material in mechanical room. |
| 03/15/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. 1) Clean clothes, boxes, other waste accumulations in laundry room - and make orderly. 2) Clean and cause storage in mechanical room to be orderly. |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 104.7.2 Technical assistance. To determine the acceptability of technologies, processes, products, facilities, materials and uses attending the design, operation or use of a building or premises subject to inspection by the fire code official, the fire code official is authorized to require the owner or agent to provide, without charge to the jurisdiction, a technical opinion and report. Provide documentation ( by a certified electrical inspector) that the extension cord wired to the refridgerator in the kitchen is in accordance with ICC Electrical Code. |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Remove extension cords in 1) Mechanical room 2) Laundry room 3) Outdoor patio area near stereo. |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Place all open wiring splices in a junction box or remove. 1) In dorm corridors where signs have been removed. 2) In south east hallway above fire extinguisher. 3) On hot water heater in mechanical room. |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace covers for: 1) 3 outlets in kitchen & kitchen closet 2) light switch in kitchen near exit and behind icemaker 3) all other missing plates in rooms and halls. |
| 03/15/2007 | VIOL - FIRE RESIST.RATED CONST | NSPRENGE | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. This has been referred to the building official for inspection. |
| 03/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | 901.4.1 Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. You are hereby ordered to have a full system sprinkler flow test by a certified sprinkler service company and provide documentation of such. |
| 03/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | 901.7 Systems out of service. Where a required fire protection system is out of service, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. You are hereby ordered to provide fire watch until your system is restored to normal working order by a certified alarm system company providing your service. Per our conversation, fire watch will be provided until the company arrives ( estimated time was 2 hours per John on 3/9/07 ). |
| 03/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | 907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Single- or multiple-station smoke alarms shall be installed and maintained in each room used for sleeping purposes. Replace smoke detector in John's room. |
| 03/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | 907.20 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with this section and Chapter 7 of NFPA 72. You are hereby ordered to have a full alarm test inspection of your alarm system ( to be repeated annually) and provide proper documentation of such by a a certified fire alarm inspection/ maintanence company. |
| 03/15/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Cause your emergency lighting to be powered:All dorm exit corridors ( hallways ). |
| 03/15/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. Replace handle on sliding glass door on W side of building near kitchen. |
| 03/15/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Remove surface bolt on kitchen pantry door. |
| 03/15/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Replace exit signs removed in the 1)downstairs corridor (nearest to the kitchen/ living room.) 2) SE corridor (upstairs) leading to exterior exit stairs. |
| 03/15/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Cause ALL of your exit signs to be illuminated 1)In North hall way, 2) NW hall, 3) Upstairs in E (near interior stairwell). |