Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00469
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace covers for: 1) 3 outlets in kitchen & kitchen closet 2) light switch in kitchen near exit and behind icemaker 3) all other missing plates in rooms and halls. | |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Place all open wiring splices in a junction box or remove. 1) In dorm corridors where signs have been removed. 2) In south east hallway above fire extinguisher. 3) On hot water heater in mechanical room. | |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Remove extension cords in 1) Mechanical room 2) Laundry room 3) Outdoor patio area near stereo. | |
| 03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 104.7.2 Technical assistance. To determine the acceptability of technologies, processes, products, facilities, materials and uses attending the design, operation or use of a building or premises subject to inspection by the fire code official, the fire code official is authorized to require the owner or agent to provide, without charge to the jurisdiction, a technical opinion and report. Provide documentation ( by a certified electrical inspector) that the extension cord wired to the refridgerator in the kitchen is in accordance with ICC Electrical Code. |