Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR00250
Case Details
Entered Date:
02/01/2007
Applicant:
MILLENNIUM ENERGY HOLDINGS INC
Description:
FPI conducted Friday 1/25/07
Outstanding Inspections
Case Number: T07FR00250
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2.3 - Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____ Remove storage from electrical room. |
02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove extension cord and/or replace with approved permanent electrical power source, outside pump room #1. |
02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.3 - A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel, near north door. _____ Clear area in front of electrical panel, compressor room, exterior, east of building. |
02/05/2007 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____ Replace missing ceiling tiles, multiple instances. |
02/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 903.3.1.1 - Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13. __NA___ The compressor room built on to the east side of the building shall be protected by an automatic sprinkler system. *** Systems Design determined that the area could be referred to as an "exterior walkway" and not required to be sprinklered if ALL combustables were removes from compresser area. |
02/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 906.5 - Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. _____ Relocate fire extinguisher in screen room so that it is in the path of travel. |
02/05/2007 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC1006.3 - The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate... _____ Repair emergency light near north door hazardous waste storage area. _____ Repair emergnecy light in screen room. |
02/05/2007 | VIOL - HAZARDOUS MATERIALS,GEN | DGREENLE | Correction Required | TFC 2703.5 - Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____ Label door to hazardous waste stream treetment area. _____ Label wall above hazardous waste storage, north wall. _____ Label exterior stairwell area (NE corner of building) indicating storage of compressed gas or with approved NFPA 704 signage. |
02/05/2007 | VIOL - FLAMMABLE LIQUIDS | DGREENLE | Correction Required | TFC 3404.3.2.1.3 - (Flammable Liquid Storage Cabinets) Doors shall be well fitted, self-closing and equipped with a three-point latch. _____ Repair or replace cabinet doors that are not self-closing. |
02/28/2007 | INSP - REINSPECTION | DGREENLE | Partial Approval | REINSPECTION 2/28 Items 23210 #2 & 3 emergency lights repaired 2/28 Items 23206 #2 & 3 electrical panel cleared 2/28 Item 23209 #2 fire extinguisher relocated 2/28 |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00250
Case Description: INSPECTION
Total Completed Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2007 | INSP - FULL | DGREENLE | Approved | Notes: Please provide access to your emergency management plan and records of evacuation drills. Please provide a copy of your waste drum disposal records. Romic Environment Tech Corp. 6760 W. Allison, chandler, AZ 85226-5130 A sample format for Hazardous Materials Management Plans (HMMP) from UFC1997 is included. Flammable liquid storage cabinets shall not exceed their designed capacity, even if the MAQ for the storage room is not exceeded. |
02/02/2007 | INSP - FULL | DGREENLE | Approved | Full FPI conducted 1/25/07 |
06/14/2007 | COMPL - REINSPECTION | DGREENLE | Approved |