Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/01/2007

Applicant:

MILLENNIUM ENERGY HOLDINGS INC

Description:

FPI conducted Friday 1/25/07

Outstanding Inspections

Case Number: T07FR00250
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
02/05/2007 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required TFC 315.2.3 - Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____ Remove storage from electrical room.
02/05/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove extension cord and/or replace with approved permanent electrical power source, outside pump room #1.
02/05/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.3 - A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel, near north door. _____ Clear area in front of electrical panel, compressor room, exterior, east of building.
02/05/2007 VIOL - FIRE RESIST.RATED CONST DGREENLE Correction Required TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____ Replace missing ceiling tiles, multiple instances.
02/05/2007 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 903.3.1.1 - Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13. __NA___ The compressor room built on to the east side of the building shall be protected by an automatic sprinkler system. *** Systems Design determined that the area could be referred to as an "exterior walkway" and not required to be sprinklered if ALL combustables were removes from compresser area.
02/05/2007 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 906.5 - Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. _____ Relocate fire extinguisher in screen room so that it is in the path of travel.
02/05/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC1006.3 - The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate... _____ Repair emergency light near north door hazardous waste storage area. _____ Repair emergnecy light in screen room.
02/05/2007 VIOL - HAZARDOUS MATERIALS,GEN DGREENLE Correction Required TFC 2703.5 - Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____ Label door to hazardous waste stream treetment area. _____ Label wall above hazardous waste storage, north wall. _____ Label exterior stairwell area (NE corner of building) indicating storage of compressed gas or with approved NFPA 704 signage.
02/05/2007 VIOL - FLAMMABLE LIQUIDS DGREENLE Correction Required TFC 3404.3.2.1.3 - (Flammable Liquid Storage Cabinets) Doors shall be well fitted, self-closing and equipped with a three-point latch. _____ Repair or replace cabinet doors that are not self-closing.
02/28/2007 INSP - REINSPECTION DGREENLE Partial Approval REINSPECTION 2/28 Items 23210 #2 & 3 emergency lights repaired 2/28 Items 23206 #2 & 3 electrical panel cleared 2/28 Item 23209 #2 fire extinguisher relocated 2/28

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00250
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
02/02/2007 INSP - FULL DGREENLE Approved Notes: Please provide access to your emergency management plan and records of evacuation drills. Please provide a copy of your waste drum disposal records. Romic Environment Tech Corp. 6760 W. Allison, chandler, AZ 85226-5130 A sample format for Hazardous Materials Management Plans (HMMP) from UFC1997 is included. Flammable liquid storage cabinets shall not exceed their designed capacity, even if the MAQ for the storage room is not exceeded.
02/02/2007 INSP - FULL DGREENLE Approved Full FPI conducted 1/25/07
06/14/2007 COMPL - REINSPECTION DGREENLE Approved