Case: T07FR00250

Parcel: 14101019B


Addresses:

5575 S HOUGHTON RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00250

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/05/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.5 - Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.

_____ Relocate fire extinguisher in screen room so that it is in the path of travel.
02/05/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 903.3.1.1 - Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13.

__NA___ The compressor room built on to the east side of the building shall be protected by an automatic sprinkler system.
*** Systems Design determined that the area could be referred to as an "exterior walkway" and not required to be sprinklered if ALL combustables were removes from compresser area.