Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR00250
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 906.5 - Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. _____ Relocate fire extinguisher in screen room so that it is in the path of travel. |
|
02/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 903.3.1.1 - Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13. __NA___ The compressor room built on to the east side of the building shall be protected by an automatic sprinkler system. *** Systems Design determined that the area could be referred to as an "exterior walkway" and not required to be sprinklered if ALL combustables were removes from compresser area. |