Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00250

Parcel: 14101019B


Addresses:

5575 S HOUGHTON RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00250

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/05/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove extension cord and/or replace with approved permanent electrical power source, outside pump room #1.
02/05/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 - A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

_____ Clear area in front of electrical panel, near north door.

_____ Clear area in front of electrical panel, compressor room, exterior, east of building.