Case: T07FR00250

Parcel: 14101019B


Addresses:

5575 S HOUGHTON RD

Inspection Status: Correction Required

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
02/05/2007 VIOL - HAZARDOUS MATERIALS,GEN Correction Required TFC 2703.5 - Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations
designated by the fire code official.

_____ Label door to hazardous waste stream treetment area.

_____ Label wall above hazardous waste storage, north wall.

_____ Label exterior stairwell area (NE corner of building) indicating storage of compressed gas or with approved NFPA 704 signage.