Case: T07FR00178
Case Details
Entered Date:
01/22/2007
Applicant:
BROADWAY POWER CENTER GROUP LLC
Description:
Full FPI conducted 1/19/07
Outstanding Inspections
Case Number: T07FR00178
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2007 | INSP - FULL | DGREENLE | Prior to Final Inspectn | Notes: _____ C of O to be provided upon re-inspection. If not available, manager will be in the process of acquiring it. Riser and system in back stock room not tagged, plaza-wide common system inspection complete. 1/5/07) |
01/22/2007 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2.1 - Storage shall be maintained... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ Remove storage to 18 inches or more below sprinkler head, over produce case. |
01/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.1 - Abatement of electrical hazards. _____ Repair light switch outside walk-in cooler, Meat dept. _____ Replace knock-out in electric panel, west receiving. TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels M & BD, kitchen area. TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. _____ Remove non-complying extension cord from library/book area. |
01/22/2007 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1026.3 - Exit signs shall be internally or externally illuminated. _____ Fix light in exit sign, over dairy case. _____ Fix exit sign, over door, back room. TFC 1026.5 - The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: ... 6. Group M. Provide emergency egress lighting.... _____ stock room north wall _____ electric room |
03/19/2007 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Correction Required | TFC 510.1 - Fire protection equipment shall be identified in an approved manner. _____ Provide signage on rear door indicating location of sprinkler riser, stock room. |
03/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 901.6 - Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected and tagged in accordance with this code. K-Class Extinguisher, stove/kitchen area/Deli/meat counter/front check area/Business office _____ Escutchens for sprinkler heads shall be repaired/replaced where missing. TFC 903.5 - Sprinkler systems shall be tested and maintained in accordance with Section 901. TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. _____ Sprinkler system, riser and valves shall be tested and tagged, stock room. TFC 906.6 - Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. _____ Provide approved signage locating extinguishers. TFC 904.11.6.4 - Hood System Service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. _____The hood exhaust and extinguishing systems shall be inspected and tagged. TFC 905.9 - Valve supervision. Valves controlling water supplies shall be supervised in the open position so that a change in the normal position of the valve will generate a supervisory signal at the supervising station required by Section 903.4. Where a fire alarm system is provided, a signal shall also be transmitted to the control unit. Exceptions: 2. Valves locked in the normal position and inspected as provided in this code in buildings not equipped with a fire alarm system. _____ Connect electric alarm for sprinkler system main valve, stock room (or provide approved lock for valve per NFPA 13). |
03/20/2007 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____ Replace missing ceiling tiles. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00178
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2007 | COMPL - REINSPECTION | DGREENLE | Approved | Approved 5/14/07 |