Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00178

Parcel: 133231430


Addresses:

7877 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00178

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/22/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1026.3 - Exit signs shall be internally or externally illuminated.

_____ Fix light in exit sign, over dairy case.

_____ Fix exit sign, over door, back room.

TFC 1026.5 - The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress:
... 6. Group M.
Provide emergency egress lighting....

_____ stock room north wall

_____ electric room