Case: T07FR00178

Parcel: 133231430


Addresses:

7877 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
01/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 - Abatement of electrical hazards.

_____ Repair light switch outside walk-in cooler, Meat dept.

_____ Replace knock-out in electric panel, west receiving.

TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area in front of electrical panels M & BD, kitchen area.

TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed.

_____ Remove non-complying extension cord from library/book area.