Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 - Abatement of electrical hazards. _____ Repair light switch outside walk-in cooler, Meat dept. _____ Replace knock-out in electric panel, west receiving. TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels M & BD, kitchen area. TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. _____ Remove non-complying extension cord from library/book area. |