Case: T05FR01466
Case Details
Entered Date:
09/20/2005
Applicant:
GUMM JOHN GLEN REVOCABLE TRUST
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01466
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 09/21/2005 | VIOL - EMERGENCY PLAN/PREPARE | JVALENZU | Violation | 407.4 - persons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled, or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak, or spill. |
| 09/21/2005 | VIOL - INDUSTRIAL OVENS | JVALENZU | Violation | 2104.2 - each industrial oven shall be provided with an approved manual fuel shutoff valve in accordance with the International Mechanical Code. |
| 09/21/2005 | VIOL - INDUSTRIAL OVENS | JVALENZU | Violation | 2106.1 - class A and B ovens shall be protected by an approved automatic fire-extinguishing system. |
Completed Inspections
Case Status: FIELD
Case Number: T05FR01466
Case Description: INSPECTION
Total Completed Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | VIOL - FLAMMABLE FINISHES | JVALENZU | Approved | 1504.3 |
| 10/10/2005 | VIOL - FLAMMABLE FINISHES | JVALENZU | Approved | 1504.2.1 |
| 10/10/2005 | VIOL - FLAMMABLE FINISHES | JVALENZU | Approved | 1504.6.4 |
| 10/10/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Approved | 2703.2.5 |
| 10/10/2005 | VIOL - MEANS OF EGRESS | JVALENZU | Approved | 1003.6 |
| 10/10/2005 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Approved | 605.3, 605.6, 605.5 |
| 10/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | JVALENZU | Approved | 906.7 |
| 10/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | JVALENZU | Approved | 901.6 |
| 10/10/2005 | VIOL - FIRE SERVICE FEATURES | JVALENZU | Approved | 505.1 |
| 12/05/2005 | VIOL - ADMINISTRATION | JVALENZU | Approved | Stop work order has been terminated by appeal to fire code official, Ch Uthe, to allow work to be performed during sprinkler system installation. |