Case: T05FR01466

Parcel: 12416027C


Addresses:

628 E 20TH ST

Inspection Status: Compliance

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
10/10/2005 VIOL - HAZARDOUS MATERIALS,GEN Compliance 2703.2.5
09/21/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation 2703.2.5 - empty containers and tanks previously used for the storage of hazardous materials shall be free from residue material or maintained as specified for the storage of hazardous material.
- several recycled buckets
09/21/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation 2703.5 - visible hazard identification signs as specified in NFPA 704 shall be placed on stationary containers and above ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used, or handled.
09/21/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation 2703.3 - hazardous materials in any quantity shall not be released.
- provide and use covers or lids for containers containing hazardous materials throughout production areas. drums and buckets.
09/21/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation 2705.2.1.3 - buildings, rooms, or areas where hazardous material liquids are dispensed into vessels exceeding a 1.3 gallon capacity or used in open systems exceeding a 5.3 gallon capacity shall be provided with spill control
09/21/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation 2705.2.1.4 - buildings, rooms, or areas where hazardous materials are dispensed or used in open systems shall be provided with secondary containment when the individual vessel or systme exceeds 1.3 gallons or multiple vessels or systems exceeds 5.3 gallons
09/21/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation table 2703.1.1(1) - maximum allowable quantity of a flammable liquid is: Class IA = 30 gal Class IB = 60 gal Class IC = 90 gal. The maximum allowable quantity shall be increased 100 percent when stored in approved storage cabinets.
The maximum allowable quantity of combustible liquids is:
Class II = 120 gallons. The maximum allowable quantity shall be increased 100 percent when stored in approved storage cabinets.

the maximum allowable quantity of corrosive hazardous materials in storage and use-open is 500 gallons

- paint in southeast office refrigerator, paint in 2 storage cabinets in wet paint room, paint on shelves in wet paint room, 55 gal drum of racing fuel in wet paint room.