Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - HAZARDOUS MATERIALS,GEN
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Compliance | 2703.2.5 | |
| 09/21/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | 2703.2.5 - empty containers and tanks previously used for the storage of hazardous materials shall be free from residue material or maintained as specified for the storage of hazardous material. - several recycled buckets |
|
| 09/21/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | 2703.5 - visible hazard identification signs as specified in NFPA 704 shall be placed on stationary containers and above ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used, or handled. | |
| 09/21/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | 2703.3 - hazardous materials in any quantity shall not be released. - provide and use covers or lids for containers containing hazardous materials throughout production areas. drums and buckets. |
|
| 09/21/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | 2705.2.1.3 - buildings, rooms, or areas where hazardous material liquids are dispensed into vessels exceeding a 1.3 gallon capacity or used in open systems exceeding a 5.3 gallon capacity shall be provided with spill control | |
| 09/21/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | 2705.2.1.4 - buildings, rooms, or areas where hazardous materials are dispensed or used in open systems shall be provided with secondary containment when the individual vessel or systme exceeds 1.3 gallons or multiple vessels or systems exceeds 5.3 gallons | |
| 09/21/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | table 2703.1.1(1) - maximum allowable quantity of a flammable liquid is: Class IA = 30 gal Class IB = 60 gal Class IC = 90 gal. The maximum allowable quantity shall be increased 100 percent when stored in approved storage cabinets. The maximum allowable quantity of combustible liquids is: Class II = 120 gallons. The maximum allowable quantity shall be increased 100 percent when stored in approved storage cabinets. the maximum allowable quantity of corrosive hazardous materials in storage and use-open is 500 gallons - paint in southeast office refrigerator, paint in 2 storage cabinets in wet paint room, paint on shelves in wet paint room, 55 gal drum of racing fuel in wet paint room. |