Case: T05FR01466

Parcel: 12416027C


Addresses:

628 E 20TH ST

Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/10/2005 VIOL - BUILDING SVCS & SYSTEMS Compliance 605.3, 605.6, 605.5
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation 605.6 - open junction boxes shall be prohibited
- blanks needed inside breaker panel in wet paint room and outside office door and receiving area west side, receptable box in wash room east wall
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 - extension cords shall not be used as a substitute for permanent wiring.
- toaster in west break room
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 - a working space of not less than 30''W x 36''D x 78''H shall be provided in front of electrical service equipment.
- wet paint room, receiving area