Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | 605.3, 605.6, 605.5 | |
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 - open junction boxes shall be prohibited - blanks needed inside breaker panel in wet paint room and outside office door and receiving area west side, receptable box in wash room east wall |
|
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 - extension cords shall not be used as a substitute for permanent wiring. - toaster in west break room |
|
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3 - a working space of not less than 30''W x 36''D x 78''H shall be provided in front of electrical service equipment. - wet paint room, receiving area |