Case: T05FR01466

Parcel: 12416027C


Addresses:

628 E 20TH ST

Inspection Status: Compliance

Inspection History: VIOL - FLAMMABLE FINISHES

Date Description Inspector Results Comments
10/10/2005 VIOL - FLAMMABLE FINISHES Compliance 1504.6.4
10/10/2005 VIOL - FLAMMABLE FINISHES Compliance 1504.2.1
10/10/2005 VIOL - FLAMMABLE FINISHES Compliance 1504.3
09/21/2005 VIOL - FLAMMABLE FINISHES Violation 1504.6 - spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system which also protects exhaust plenums, exhaust ducts, and both sides of dry filters.
- all booths
09/21/2005 VIOL - FLAMMABLE FINISHES Violation 1504.6.4 - portable fire extinguishers shall be provided of minimum rating 40B within 30' travel distance to the extinguisher.
- all booths and ovens
09/21/2005 VIOL - FLAMMABLE FINISHES Violation 1504.2.1 - spraying equipment shall be interlocked with the ventilation system such that spraying operations cannot be conducted unless the ventilation system is in operation.
- all booths
09/21/2005 VIOL - FLAMMABLE FINISHES Violation 1504.2.3 - ventilation systems shall be designed, installed, and maintained such that the average air velocity over the open face of the booth shall not be less than 100 linear feet per minute.
09/21/2005 VIOL - FLAMMABLE FINISHES Violation 1504.2.5 - each spray booth shall have a duct discharging to the outside.
- powder booth 2
09/21/2005 VIOL - FLAMMABLE FINISHES Violation 1504.3 - exhaust filters shall be required
- powder booth 3