Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - FLAMMABLE FINISHES
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | VIOL - FLAMMABLE FINISHES | Compliance | 1504.6.4 | |
| 10/10/2005 | VIOL - FLAMMABLE FINISHES | Compliance | 1504.2.1 | |
| 10/10/2005 | VIOL - FLAMMABLE FINISHES | Compliance | 1504.3 | |
| 09/21/2005 | VIOL - FLAMMABLE FINISHES | Violation | 1504.6 - spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system which also protects exhaust plenums, exhaust ducts, and both sides of dry filters. - all booths |
|
| 09/21/2005 | VIOL - FLAMMABLE FINISHES | Violation | 1504.6.4 - portable fire extinguishers shall be provided of minimum rating 40B within 30' travel distance to the extinguisher. - all booths and ovens |
|
| 09/21/2005 | VIOL - FLAMMABLE FINISHES | Violation | 1504.2.1 - spraying equipment shall be interlocked with the ventilation system such that spraying operations cannot be conducted unless the ventilation system is in operation. - all booths |
|
| 09/21/2005 | VIOL - FLAMMABLE FINISHES | Violation | 1504.2.3 - ventilation systems shall be designed, installed, and maintained such that the average air velocity over the open face of the booth shall not be less than 100 linear feet per minute. | |
| 09/21/2005 | VIOL - FLAMMABLE FINISHES | Violation | 1504.2.5 - each spray booth shall have a duct discharging to the outside. - powder booth 2 |
|
| 09/21/2005 | VIOL - FLAMMABLE FINISHES | Violation | 1504.3 - exhaust filters shall be required - powder booth 3 |