Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/22/2005

Applicant:

D RAGEL ENTERPRISES LLC

Description:

Inspection

Outstanding Inspections

Case Number: T05FR01305
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/15/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy.
08/15/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- MSDS for all hazardous materials shall be readily available on the premises.
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. 1. Shop light wires run through ceiling. 2. wires on East exterior wall out of conduit
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" W, 36" D, 78" H shall be provided in front of electrical service equipment.
08/15/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. N wall outside
08/15/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (Chemical room)
08/15/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (WPS bldg)
08/15/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- The path of egress trave shall be free of obstructions and uninterrupted. 1. soda machine obstructing path 2. gate not permitted in path
08/15/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- Emergency lighting shall be provided in the event of a power failure.
08/15/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.9- Panic hardware shall have a maximum unlatching force of 15 lbs. (East door)
08/15/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.1- Exit doors shall be marked by an approved exit sign readily visible from any direction of travel. (East side of bldg going West)
08/15/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Exit sign shall be internally or externally illuminated. (East side of bldg going West)
08/15/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.1.1(1)- Maximum allowable quantity per control area is as follows: Class I-A=30 gals, Class I-B=60 gals, Class I-C=90 gals.
08/15/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.3- Hazardous materials in any quantity shall not be released onto the ground. Oil on ground, East side of property
08/15/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.7.1- No smoking signs shall be provided within 25 feet of storage for flammable liquids.
08/15/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2704.3- Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation.
08/15/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3403.5.1- Warning signs of the hazard of flammable liquids shall have white lettering on a red background and shall read: DANGER-FLAMMABLE LIQUIDS. The letters shall not be less than 3" in height with a .5" stroke.
08/15/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3404.3.2.3- Not more than 3 storage cabinets shall be located in a single fire area.