Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T05FR01305
Case Details
Entered Date:
08/22/2005
Applicant:
D RAGEL ENTERPRISES LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01305
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
08/15/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy. |
08/15/2005 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 407.2- MSDS for all hazardous materials shall be readily available on the premises. |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. Shop light wires run through ceiling. 2. wires on East exterior wall out of conduit |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" W, 36" D, 78" H shall be provided in front of electrical service equipment. |
08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. N wall outside |
08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (Chemical room) |
08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (WPS bldg) |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress trave shall be free of obstructions and uninterrupted. 1. soda machine obstructing path 2. gate not permitted in path |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Emergency lighting shall be provided in the event of a power failure. |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.9- Panic hardware shall have a maximum unlatching force of 15 lbs. (East door) |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.1- Exit doors shall be marked by an approved exit sign readily visible from any direction of travel. (East side of bldg going West) |
08/15/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.2- Exit sign shall be internally or externally illuminated. (East side of bldg going West) |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.1.1(1)- Maximum allowable quantity per control area is as follows: Class I-A=30 gals, Class I-B=60 gals, Class I-C=90 gals. |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.3- Hazardous materials in any quantity shall not be released onto the ground. Oil on ground, East side of property |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.7.1- No smoking signs shall be provided within 25 feet of storage for flammable liquids. |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2704.3- Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation. |
08/15/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3403.5.1- Warning signs of the hazard of flammable liquids shall have white lettering on a red background and shall read: DANGER-FLAMMABLE LIQUIDS. The letters shall not be less than 3" in height with a .5" stroke. |
08/15/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3404.3.2.3- Not more than 3 storage cabinets shall be located in a single fire area. |