Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - HAZARDOUS MATERIALS,GEN
Case Number - T05FR01305
Inspection Description - VIOL - HAZARDOUS MATERIALS,GEN
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | TFC 2703.1.1(1)- Maximum allowable quantity per control area is as follows: Class I-A=30 gals, Class I-B=60 gals, Class I-C=90 gals. | |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | TFC 2703.7.1- No smoking signs shall be provided within 25 feet of storage for flammable liquids. | |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | TFC 2704.3- Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation. | |
08/15/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Violation | TFC 2703.3- Hazardous materials in any quantity shall not be released onto the ground. Oil on ground, East side of property |