Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. Shop light wires run through ceiling. 2. wires on East exterior wall out of conduit |
|
| 08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. N wall outside | |
| 08/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of not less than 30" W, 36" D, 78" H shall be provided in front of electrical service equipment. |