Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T05FR01305
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2005 | VIOL - MEANS OF EGRESS | Violation | TFC 1008.1.9- Panic hardware shall have a maximum unlatching force of 15 lbs. (East door) | |
08/15/2005 | VIOL - MEANS OF EGRESS | Violation | TFC 1003.6- The path of egress trave shall be free of obstructions and uninterrupted. 1. soda machine obstructing path 2. gate not permitted in path |
|
08/15/2005 | VIOL - MEANS OF EGRESS | Violation | TFC 1011.1- Exit doors shall be marked by an approved exit sign readily visible from any direction of travel. (East side of bldg going West) | |
08/15/2005 | VIOL - MEANS OF EGRESS | Violation | TFC 1011.2- Exit sign shall be internally or externally illuminated. (East side of bldg going West) | |
08/15/2005 | VIOL - MEANS OF EGRESS | Violation | TFC 1006.3- Emergency lighting shall be provided in the event of a power failure. |