Case Details

Status:

COMPLETE

Type:

COMPLAINT (RESIDENTIAL)
Address:

Entered Date:

08/04/2005

Applicant:

HUB PROPERTIES TRUST

Description:

inspection

Outstanding Inspections

Case Number: T05FR01222
Case Status: COMPLETE
Case Description: COMPLAINT (RESIDENTIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
COMPLIANCE None Not Inspected

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01222
Case Description: COMPLAINT (RESIDENTIAL)
Total Completed Inspections - 3
End Date Description Inspector Results Comments
11/22/2005 INSP - FULL EGRIFFIN Approved
11/22/2005 VIOL - FIRE PROTECTION SYSTEMS EGRIFFIN Approved Fire alarms shall be of the following decibels as per IFC 907.10.2 Still to be completed is the answering of complaints by the occupants of the building of not hearing the fire alarm. Proof must be submitted by contractor of sound measurement or by TFD sound measurement. Alarms shall be between 60- 75 dBA throughout building. Please contact me for a date for sound measurement or show other proof by contractors that the all alarms can be heard through out building as per code requirements, by 12-14-05 In addition; no strobes are on the 14th floor, 15th, 16th, and 17th.
11/22/2005 INSP - REINSPECTION EGRIFFIN Approved