Case: T05FR01222

Parcel: 11712098A


Addresses:

1 S CHURCH AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR01222

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2006 INSP - FULL Approved
11/22/2005 INSP - FULL Approved
08/04/2005 INSP - FULL Violation 1). Submit copy of testing dates of emergency power system to TFD. IFC 604.3.2
2). Hole next to exit light on 19th floor shall be repaired. IFC 703.1
3). Fire alarm test and inspection report shall be submitted to TFD IFC 906.1. All required repairs shall be completed.
4). Automatic fire sprinkler report shall be submitted to TFD 906.1. All required repairs shall be completed.
5). Fire pump test report shall be submitted to TFD. 906.1
6). 18th floor Unisource break room: Trashcans are in exit width. Shall always be clear of exit width IFC 1027.3
7). The following areas have storage within 2 feet of ceiling height:
18th Lawyers title-small closet, 15th floor file room, 12th floor, "Hern" office, Suite 1120 break room, Fennemore breakroom, Suite 900 breakroom, Suite 900 file storage room, 7th floor copy room (suitcases), 1st floor Unisource.
The Fire Code states:
315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in areas of buildings and a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
8). Fire drill shall be conducted. Date shall be determined by 9-7-05. IFC 404.1
9). The following holes in fire resistive walls, replace UL Classified fire stopping, and or separations shall be repaired. IFC 703.1, IFC 703.1.1
13th floor Mechanical room, 16th floor electrical room, 12th floor Mechanical room, 12th floor electrical room, 9th floor electrical room, 8th floor electrical room,
10). 28" aisles shall be maintained in the following areas IFC 1003.3.4: FBI computer room, 15th floor file room.
11). Remove table from stairwell on 17th floor. IFC 1023.2.
12). All doors with door closure shall remain closed. This is extremely important on engineering floor. IFC 703.2.2. Keep doors closed on engineering floor. Remove doorstops.
13). 3rd floor. Remove extension cord from around chemical storage area. IFC 605.5
14). Suite 940. Mount fire extinguisher. IFC 906.7
15). Check portable fire extinguishers every 30 days as per NFPA 10 standards require. IFC 906.1