Case: T05FR01222

Parcel: 11712098A


Addresses:

1 S CHURCH AV


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T05FR01222

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2006 VIOL - FIRE PROTECTION SYSTEMS Approved all ok
11/22/2005 VIOL - FIRE PROTECTION SYSTEMS Violation Fire alarms shall be of the following decibels as per IFC 907.10.2

Still to be completed is the answering of complaints by the occupants of the building of not hearing the fire alarm. Proof must be submitted by contractor of sound measurement or by TFD sound measurement.

Alarms shall be between 60- 75 dBA throughout building.

Please contact me for a date for sound measurement or show other proof by contractors that the all alarms can be heard through out building as per code requirements, by 12-14-05

In addition; no strobes are on the 14th floor, 15th, 16th, and 17th.