Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | all ok | |
| 11/22/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Fire alarms shall be of the following decibels as per IFC 907.10.2 Still to be completed is the answering of complaints by the occupants of the building of not hearing the fire alarm. Proof must be submitted by contractor of sound measurement or by TFD sound measurement. Alarms shall be between 60- 75 dBA throughout building. Please contact me for a date for sound measurement or show other proof by contractors that the all alarms can be heard through out building as per code requirements, by 12-14-05 In addition; no strobes are on the 14th floor, 15th, 16th, and 17th. |