Case: T05FR00531
Case Details
Entered Date:
04/26/2005
Applicant:
S&L BUILDING PARTNERS LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00531
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 34
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 04/26/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- Certificate of Occupancy. No building or structure shall be used or occupied...until the building official has issued a C of O. |
| 04/26/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.2- Combustible materials shall not be stored in exits or exit enclosures. (outside west door) |
| 04/26/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.4- Storage of combustibles shall not be permitted under stairs unless it is protected on the storage side as required for 1 hour fire resistive rated construction. |
| 04/26/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 504.2- Exterior doors that have been rendered non-functional and that retain the appearance of a functional door shall have a sign affixed to the exterior side of the door with the words "THIS DOOR BLOCKED". The letters shall be at least 6" in height on a contrasting background. |
| 04/26/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 504.2- Exterior doors...non-functional. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Cover plate shall be installed. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. Electrical cord plugged into surge protector needs repair (Steve's office). |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" width x 36" depth x 78" height shall be provided in front of electrical service equipment. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space...30 x 36 x 78...electrical service equipment. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space...equipment. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be used as permanent wiring. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Electrical panel shall have blank installed in opening. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. Receptacles behind soda machines need cover plates. |
| 04/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open wiring splices shall be prohibited. Cords shall be continuous from appliance to receptacle (2 heating units). |
| 04/26/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.4- Rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure. |
| 04/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be inspected monthly and serviced annually. (several throughout) |
| 04/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.2- Fire extinguishers shall be maintained in accordance with NFPA 10. Extinguisher sign shall be removed from beam. |
| 04/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC Fire extinguishers shall be installed on their hanger or bracket and anchored securely. (every 3000 sq. ft) |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | 1009.11- Stairs shall have handrails. see page 2. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- Obstructions to exits shall not be placed in the required width and exits shall not be obstructed in any manner. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.2- Exit doors shall swing in the direction of exit travel. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8- Doors shall be openable...effort. ( SW office) |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8- Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1009.11- Stairways shall have handrails on each side and shall be adequate in strength and attachment. Handrail height shall be uniform, not less than 34" and not more than 38", measured from tread nosings. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.1- Exit signs are required in rooms or areas which require 2 or more exits. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible sign. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.2- Exit signs shall be internally or externally illuminated at all times. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1014.1- 2 exits from any space shall be provided when the occupant load exceeds 50. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1016.2- The minimum corridor width shall not be less than 44". When the occupant load is 50 or less, 36" is the minimum width. Buildings with only 1 exit and less than 50 occupants, the maximum travel distance to an exit is 75'. |
| 04/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC The means of egress shall be illuminated at all times the building space is occupied. |
| 04/26/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.9.8- Incompatible materials shall be separated by a minimum of 35 feet. Flammables and combustibles shall be separated from hot work areas. |
| 04/26/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3403.1.3- Class 1 electrical equipment is required within 10 feet of a solvent tank. |
| 08/21/2007 | INSP - REINSPECTION | JLANGEJA | Continued | met with Steve to discuss progress of changes. Introduced MA85 as the contact person. |