Inspection

Outstanding Inspections

Case Number: T05FR00531
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 34
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/26/2005 VIOL - ADMINISTRATION JLANGEJA Violation TBC 110.1- Certificate of Occupancy. No building or structure shall be used or occupied...until the building official has issued a C of O.
04/26/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.2- Combustible materials shall not be stored in exits or exit enclosures. (outside west door)
04/26/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.4- Storage of combustibles shall not be permitted under stairs unless it is protected on the storage side as required for 1 hour fire resistive rated construction.
04/26/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation TFC 504.2- Exterior doors that have been rendered non-functional and that retain the appearance of a functional door shall have a sign affixed to the exterior side of the door with the words "THIS DOOR BLOCKED". The letters shall be at least 6" in height on a contrasting background.
04/26/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation TFC 504.2- Exterior doors...non-functional.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Cover plate shall be installed.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. Electrical cord plugged into surge protector needs repair (Steve's office).
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" width x 36" depth x 78" height shall be provided in front of electrical service equipment.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space...30 x 36 x 78...electrical service equipment.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space...equipment.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be used as permanent wiring.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Electrical panel shall have blank installed in opening.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes shall be prohibited. Receptacles behind soda machines need cover plates.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open wiring splices shall be prohibited. Cords shall be continuous from appliance to receptacle (2 heating units).
04/26/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.4- Rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure.
04/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be inspected monthly and serviced annually. (several throughout)
04/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.2- Fire extinguishers shall be maintained in accordance with NFPA 10. Extinguisher sign shall be removed from beam.
04/26/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC Fire extinguishers shall be installed on their hanger or bracket and anchored securely. (every 3000 sq. ft)
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation 1009.11- Stairs shall have handrails. see page 2.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Obstructions to exits shall not be placed in the required width and exits shall not be obstructed in any manner.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.2- Exit doors shall swing in the direction of exit travel.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8- Doors shall be openable...effort. ( SW office)
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8- Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1009.11- Stairways shall have handrails on each side and shall be adequate in strength and attachment. Handrail height shall be uniform, not less than 34" and not more than 38", measured from tread nosings.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.1- Exit signs are required in rooms or areas which require 2 or more exits. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible sign.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.2- Exit signs shall be internally or externally illuminated at all times.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1014.1- 2 exits from any space shall be provided when the occupant load exceeds 50.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1016.2- The minimum corridor width shall not be less than 44". When the occupant load is 50 or less, 36" is the minimum width. Buildings with only 1 exit and less than 50 occupants, the maximum travel distance to an exit is 75'.
04/26/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC The means of egress shall be illuminated at all times the building space is occupied.
04/26/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.9.8- Incompatible materials shall be separated by a minimum of 35 feet. Flammables and combustibles shall be separated from hot work areas.
04/26/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3403.1.3- Class 1 electrical equipment is required within 10 feet of a solvent tank.
08/21/2007 INSP - REINSPECTION JLANGEJA Continued met with Steve to discuss progress of changes. Introduced MA85 as the contact person.