Case: T05FR00531

Parcel: 12418187B


Addresses:

1401 E 20TH ST

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Identified electrical hazards shall be abated. Electrical cord plugged into surge protector needs repair (Steve's office).
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open wiring splices shall be prohibited. Cords shall be continuous from appliance to receptacle (2 heating units).
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" width x 36" depth x 78" height shall be provided in front of electrical service equipment.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes shall be prohibited. Receptacles behind soda machines need cover plates.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Cover plate shall be installed.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space...30 x 36 x 78...electrical service equipment.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be used as permanent wiring.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Electrical panel shall have blank installed in opening.
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space...equipment.