Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1008.1.8- Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1009.11- Stairways shall have handrails on each side and shall be adequate in strength and attachment. Handrail height shall be uniform, not less than 34" and not more than 38", measured from tread nosings. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
1009.11- Stairs shall have handrails. see page 2. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1008.1.8- Doors shall be openable...effort. ( SW office) |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1014.1- 2 exits from any space shall be provided when the occupant load exceeds 50. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1008.1.2- Exit doors shall swing in the direction of exit travel. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC The means of egress shall be illuminated at all times the building space is occupied. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1011.1- Exit signs are required in rooms or areas which require 2 or more exits. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible sign. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1011.2- Exit signs shall be internally or externally illuminated at all times. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1003.6- Obstructions to exits shall not be placed in the required width and exits shall not be obstructed in any manner. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1016.2- The minimum corridor width shall not be less than 44". When the occupant load is 50 or less, 36" is the minimum width. Buildings with only 1 exit and less than 50 occupants, the maximum travel distance to an exit is 75'. |
| 04/26/2005 |
VIOL - MEANS OF EGRESS |
|
Violation |
TFC 1008.1.8.4- Manually operated flush bolts or surface bolts are not permitted. |