Permit Number: T22CM06403
Parcel: 12709011P

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM06403
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the proposed sink. Reference: Sections 303.4 and 402, IPC 2018.
2. Show how hot or tempered water is to be supplied to the proposed sink. Reference: Section 607.1, IPC 2018
09/01/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/01/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/01/2022 ROBERT SHERRY WATER REVIEW Completed
09/02/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06403

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Sheet A1 Provide ADA Access to stage.
Sheet A1 Provide with of exit access, provide ADA door clearance for opening
Sheet A1 Provide Accessible path of travel to Accessible parking and the public way from all required exits.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/07/2022 PAUL CAMARENA ZONING REVIEW Approved
09/07/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/13/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Provide a note requiring the new or relocated lighted Exit Signs and battery back-up lighting are to be connected to “Unswitched Lighting Circuit”.

Relocated ceiling lighting to utilize existing branch circuits.

Provide lighting controls for the new classrooms and storage, assembly areas where applicable.

Verify egress lighting is provided for. IBC section 1008.3 (1), (2), (3).

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
09/16/2022 JVINCEN1 FIRE REVIEW Approved