Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM06403
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/01/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for the proposed sink. Reference: Sections 303.4 and 402, IPC 2018. 2. Show how hot or tempered water is to be supplied to the proposed sink. Reference: Section 607.1, IPC 2018 |
| 09/01/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/01/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 09/01/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/02/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Activity Number: T22CM06403 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Sheet A1 Provide ADA Access to stage. Sheet A1 Provide with of exit access, provide ADA door clearance for opening Sheet A1 Provide Accessible path of travel to Accessible parking and the public way from all required exits. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 09/07/2022 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
| 09/07/2022 | PCAMARE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/13/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Provide a note requiring the new or relocated lighted Exit Signs and battery back-up lighting are to be connected to “Unswitched Lighting Circuit”. Relocated ceiling lighting to utilize existing branch circuits. Provide lighting controls for the new classrooms and storage, assembly areas where applicable. Verify egress lighting is provided for. IBC section 1008.3 (1), (2), (3). Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 09/16/2022 | JVINCEN1 | FIRE | REVIEW | Approved |