Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03148
Parcel: 11706077R

Address:
211 N 4TH AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T22CM03148
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide a site plan showing the location of the temporary electrical service on the building site and associated downstream equipment.

2. Provide a complete grounding detail that complies with NEC art 250.53A(2).

3. Provide information as to what the sqaure blocks with the number inside shown on the riser diagram for each floor represent. Plan sheet 1.01

4. Provide more detail on the riser diagram for the conduits and or cable types, conductors sizes and types that are feeding the sqaure boxes with the numbers 1 and 2 after the panel boards on each level. Plan Sheet 1.01.

5. Indicate how (wiring methods) the Buckhoist and Concrete Pumps will connect to the disconnects.

Ref’ 2018 IBC sec 107.2.1, 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2022 VVERA1 OUT TO CUSTOMER Completed