Permit Number: T22CM02219
Parcel: 11706077R

Address:
211 N 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM02219
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet A0.01 Section 403.3.3 shows that you are adding an additional supply should it be 403.3.2 and if the building is not 420' a secondary supply would not be required?
Sheet A0.01 Section 403.4 reminder your are also a R2 and local amendments shall apply for the fire alarm system
Sheet A0.01 Section 403.4 ERRC note 510 of the IFC shall also read Building shall be tested for ERRC by PCWIN and the report provided to TFD
Sheet A0.01 Chapter 9 please check our local amendments for R-2 requirements
Sheet A0.01 Chapter 17 Required special inspections and test - 1705.18 Testing for smoke control shall be added
Sheet A0.01 Chapter 30, 301.2 shall be added as a note

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033
Fire Plans Examiner
05/31/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM02219

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical plans submitted. No mechanical review required at this time.


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E0.01 ELECTRICAL LEGEND AND SYMBOLS: No electrical issues
E0.02 DRAWING INDEX: No electrical issues
E0.03 LIGHTING FIXTURE SCHEDULE: No electrical issues
E1.01 E1 - SITE PLAN: 2nd Utility feed equipment not shown.
E2.00L LEVEL B1 - LIGHTING - AREA A: No electrical issues
E2.00P LEVEL B1 - POWER - AREA A: No electrical issues
E4.00 ENLARGED ELECTRIC ROOMS: No electrical issues
E5.00 ELECTRICAL RISER LEGENDS AND DETAILS: No electrical issues
Only the above sheets have permit approval (with comments) for site work.


PLUMBING REVIEW COMMENTS:
Denied
Second Foundation Plumbing Review:
1). SAME-Details #2 & #3 on plan page P0.01F need to have the sump basins vented. --IPC 712.3.2 **Details not updated**
2 thru 5 OK
6).OK - Exterior drinking fountain will need to be protected from receiving storm water on building plans.
7 thru 9 OK
10). SAME- indicate the GPM load of the all the vertical foundation drainage Mat system connections on each affected plumbing page. -IPC 1106.2 ** GPM loads still not shown at the matt drainage system connections**
11). OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/14/2022 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review