Permit Number: T21CM01719
Parcel: 11515214B

Address:
785 W SAHUARO ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM01719
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01719


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Partial Set of Calculations submitted (Total 17 pages). Submit rest of the Calculations as called out on the response letter to include the following.
1. Provide Wind Load Calculations for the Building per Section 1609 of International Building Code 2018.
2. Provide Seismic Calculations for the Building per Section 1613 of International Building Code 2018.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.

BUILDING REVIEW COMMENTS:
Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2022 NGARCIA3 OUT TO CUSTOMER Completed